Wishlist

Remote power supply for fire detection systems / 6 A / 5 NAC or 24 Vdc auxiliary outputs / compatible with 12 or 24 V FACPs

  • $ 14,299.00
  • Brand: HONEYWELL
  • Availability: In stock
  • SKU: HPF-PS6B

The HPF-PS6B is a Honeywell Gamewell-FCI PS series remote power supply, a direct replacement for the FCPS series, with a 6-amp capacity. It provides 24 VDC power for Notification Appliance...

Tags: categoria:Detección de Fuego , marca:HONEYWELL , proveedor:Syscom , sku:HPF-PS6B , supplier:Syscom , syscom

The HPF-PS6B is a Honeywell Gamewell-FCI PS series remote power supply, a direct replacement for the FCPS series, with a 6-amp capacity. It provides 24 VDC power for Notification Appliance Circuits (NACs) and for auxiliary loads such as detectors, annunciators, and door holders. It connects to any 12 or 24 V fire alarm control panel (FACP), or can operate as a standalone supply in commercial and industrial fire detection systems. It integrates with optional addressable modules (AOM, AMM, MMO) and the ZNAC-PS card for Class B to Class A conversion.

Key Features

  • Up to 5 output circuits of 24 VDC configurable as NAC or auxiliary, Class A or B
  • Converts Class B wiring to Class A with the optional ZNAC-PS card
  • 2 fully isolated input/control circuits, programmable to any output
  • Integrated battery charger: up to 18 Ah in the cabinet, 33 Ah in an external cabinet
  • UL-Listed NAC synchronization with System Sensor, Wheelock, Gentex, or AMSECO devices
  • 2 Form C normally closed relays for AC fault and general trouble
  • Heavy-gauge steel cabinet with lock and corrosion-resistant finish

Technical Specifications

Output Current6 A maximum, 3 A maximum per circuit
Input Power120 VAC, 50/60 Hz, 5.0 A maximum
Configurable Outputs5 Class A/B NAC or 24 VDC auxiliary circuits
Control Inputs2 isolated circuits, 9 to 32 VDC
Battery ChargerUp to 33 Ah external (18 Ah in cabinet); 27.6 VDC float
Dimensions50.8 x 36.83 x 8.9 cm
Weight10.9 kg with two 7 Ah batteries; 17.7 kg with two 18 Ah batteries
Standards and ListingsNFPA 72, UL 864, UL 1481; UL S24562; CSFM 7315-1637:0505; FDNY; FM