Wishlist

Conventional Zone Input Module for 4" Box, Class A and B (0400-01840)

  • $ 1,399.00
  • Brand: HOCHIKI
  • Availability: 2 In stock
  • SKU: CZM

Main Features Monitors: 2-wire 24VDC conventional smoke detectors Supervision: External power source supply Reported states: Normal, Open, or Alarm Power requirement: 24VDC external power source Compatibility: Class A or Class...

Tags: categoria:Detección de Fuego , marca:HOCHIKI , proveedor:Syscom , sku:CZM , supplier:Syscom , syscom

Main Features

  • Monitors: 2-wire 24VDC conventional smoke detectors
  • Supervision: External power source supply
  • Reported states: Normal, Open, or Alarm
  • Power requirement: 24VDC external power source
  • Compatibility: Class A or Class B SLC loops

Technical Specifications

  • Supply voltage (S-SC): 25.3 ~ 39 VDC
  • Auxiliary voltage: 18.8 ~ 27.2 VDC
  • Average consumption (on S-SC line): 670µA
  • 2-wire detector loop current: 1mA Max. in standby
  • Current from auxiliary source: 60mA Max.
  • EOL resistor: 4.7K ohms
  • Maximum quantity per loop: 127
  • Alarm threshold: <1.5K ohms
  • Open circuit threshold: >10K ohms
  • Maximum loop resistance: 50 ohms (total cable length)
Operating Conditions
  • Temperature: 0°C ~ 49°C (32°F ~ 120°F)
  • Humidity: 90% RH non-condensing
Certifications
  • UL 864 9th Edition Listed
  • California State Fire Marshal 3033215
  • UL Listed 1481
Dimensions
  • 4.2" Wide x 4.7" High x 1.4" Deep
  • Mounting in 4" square electrical box
Compatibility
  • With conventional detectors
  • SLR, SIJ, SLK, SLV, DCD, DFE and SIH series
  • DCP (Digital Communication Protocol)
Installation
  • Addressable via handheld programmer
  • Programmable address: 1 to 127
  • Maximum 127 devices per SLC loop
  • Maximum 25 detectors per zone
Additional Features
  • Bi-color LED for status indication
  • Supplied with plastic cover
  • Monitoring LED visible from the outside
  • Designed for analog addressable systems
  • Reliable and fast communication in emergencies
Applications
  • Analog fire alarm systems
  • Monitoring of zones with conventional detectors
  • Systems with UL 864 9th Edition requirements
  • Commercial and industrial installations
Connections
  • TB1 connector for power supply connection
  • TB2 connector for SLC loop connection
  • Jumpers for wiring configuration
Limitations
  • Do not mix alarm and supervisory devices in the same module
  • Limited to 25 conventional detectors per zone
  • Requires correct jumper configuration based on wiring type