Key Features

  • Isolates the SLC to easily locate shorts
  • Recommended one for every 20 detectors
  • Requires T-tap wiring at each point
  • Compatible with the Silent Knight intelligent series
  • Product available by special order only
Technical Specifications
  • Operating temperature: 32° - 120° F (0° - 49° C)
  • Operating voltage: 32 VDC
  • Alarm/standby current: 92 μA
  • SLC current: 50 μA
  • Maximum SLC resistance: 50Ω
Dimensions
  • Length: 4-7/8'
  • Width: 4-7/8'
  • Depth: 7/8'
Configurations
  • Class B (Style 4) configuration
  • Class A (Style 7) configuration
  • Up to 50 devices
  • Up to 10Ω per branch

Installation Instructions

  1. Mount the extension base using #8 1-1/2' screws through the extension base mounting holes.
  2. Connect the SLC loop wiring as shown in Figure 3 or Figure 4.
  3. Connect the wiring harness to the smoke base as shown in Figure 5.
  4. Connect the harness to the connector.
  5. Connect the smoke base (P/N SD505-6AB) to the extension base (P/N 120505) using #8 1/2' screws.

Important Notes

  • Installation and wiring must be performed in accordance with NFPA 72 and local ordinances.
  • All wiring is supervised and power-limited.
  • Do not use more than 256 isolator devices (SD505-LIM or SD505-6IB) on an SLC loop.